Efektivitas pencahayaan buatan kamar crowne plaza Semarang
Artificial lighting system in the hotel building must be taken to ensure that the facilities provided can be operated with either. One way is to measure the intensity of artificial lighting using a lux meter or using an existing formula, analyzed by comparing the intensity of artificial lighting that is with SNI 03-6575-2001 about artificial lighting, and well planned maintenance. The purpose of this research is to create an artificial lighting system in accordance with SNI 03-6575-2001 about artificial lighting, and creating scheduling regular maintenance and programmed for artificial pencahyaan existing system. The data used in the study is the specification of artificial lighting and observation, measurement using a lux meter Hioki 3421. All data in the identification based on SNI 03-6575-2001. The results showed that the effectiveness of artificial lighting in the room Crowne Plaza Semarang especially lighting sleeping only 76.8%, 36% work lighting, general lighting 50%. To achieve a 100% effectiveness, the addition of lux on artificial lighting. At the end of the study formulated artificial lighting system maintenance schedule should be kept so that the rooms are always in a condition ready for occupation so there is no problems when used.
Keywords: Artificial lighting intensity, SNI, Artificial Lighting Effectiveness Analysis, Maintenance.